Emergency generators ran beyond 100-hour annual non-emergency limit

Company: Core Scientific

Subject kind
regulatory
Statement date
2026-11-02
Current status
stated

The claim, verbatim

TCEQ said Core Scientific ran eight emergency generators for non-emergency use beyond the 100 hours per year allowed: four ran 1,352-1,371 hours at one building and four ran 527-1,024 hours at another.

Source (primary)

Denton’s Core Scientific data center faces TCEQ violations due to air quality emissions - Denton Record-Chronicle (-, news_article)
View cached copy (2026-11-03)Live source ↗Archive.org ↗

Quote: “Core Scientific operated eight of its emergency generators for non-emergency use for more than the 100 hours per year allowed”